Macquarie Data Centres files A$2bn Macquarie Park plan
By Winston Su, Editor · · Add us as a preferred source on Google

At a glance
Macquarie Data Centres has filed plans for a 200MW data centre campus at 2 Alma Road, Macquarie Park, with an estimated development cost of A$2 billion.
The campus pairs two data centre buildings with a Macquarie University teaching facility and a 4,495 square metre public park.
Ausgrid has confirmed a 132kV connection is appropriate, with its proposed Wallumatta switching station as the preferred supply and first load expected in late 2029.
Cooling would come from about 135 roof-mounted air-cooled chillers, in a design the company says minimises water use.
The company says it will address the state's August 2026 data centre guidelines in its environmental impact statement, the next step after the planning department sets its requirements.
Macquarie Data Centres has filed plans for its 200MW Macquarie Engineering and Technology Campus at 2 Alma Road, Macquarie Park, in Sydney's north. A scoping report dated 27 October 2026 asks the New South Wales planning department to set its Secretary's Environmental Assessment Requirements, the studies the company must complete before the project opens for public comment. The request is listed on the state's planning portal as SSD-151494240.
When parent company Macquarie Technology Group (ASX: MAQ) exercised its option over the land in July 2026, a grid connection was among the steps it listed before construction. The scoping report says Sydney electricity distributor Ausgrid has confirmed a 132kV connection is appropriate for a campus with a maximum demand of about 350MVA to 400MVA, and names Ausgrid's proposed Wallumatta switching station as the preferred supply.
Macquarie Data Centres plans two buildings, labs and a park at Alma Road
The site covers 34,190 square metres between Talavera Road and the M2 motorway. It was subdivided from 66 Talavera Road, which keeps its existing commercial building on the other lot. A conference building and an office building, about 10,419 square metres of floor space in all, would be demolished along with their car parks. The land is zoned E3 Productivity Support, a business zone in the City of Ryde's planning controls where a data centre is permitted with consent, as are the teaching facility and the park.
In their place, Macquarie Data Centres proposes two data centre buildings of generally five to six storeys, built after an initial demolition and earthworks stage. They would generally stand 40 to 45 metres high, rising to about 50.9 metres for a small portion of rooftop fittings. That portion sits about 5.9 metres above the 45-metre incentive height, the higher limit Ryde's planning rules allow when set conditions are met, so the company will lodge a request to vary the limit with its environmental impact statement.

Of the 43,015 square metres of floor space, 6,002 go to offices, an auditorium and teaching laboratories, and the rest to the data centre. The report estimates the development cost at approximately A$2 billion, subject to final advice from a quantity surveyor.
The laboratories house a teaching, training and research facility delivered in partnership with Macquarie University, built in the first stage alongside the first data centre building. The second stage demolishes the remaining building on Alma Road, adds the second data centre building and opens Alma Park, a 4,495 square metre public park on the Alma Road frontage. Upper-level screens facing Talavera Road would carry an outdoor art gallery.
The report estimates about 2,600 jobs during construction, half of them direct. Once operating, the campus would support about 275 jobs, about 110 of them direct and including round-the-clock shift workers.
Ausgrid's proposed Wallumatta station is the campus's preferred supply
The 200MW figure is IT load, the power that reaches the servers. The campus's maximum demand of about 350MVA to 400MVA is measured in megavolt-amperes, the unit networks use to size a connection. Wallumatta is a proposed 132/33kV sub-transmission switching station, and the plans add a proposed 132kV substation on the site itself.
Initial load uptake is expected in late 2029, with demand rising in stages after that. Backup power would come from about 139 containerised generators on a gantry facing the M2, with about 3,439 kilolitres of diesel stored on site. A battery system is proposed, with its design to be submitted with the environmental impact statement.
The new campus adds to Macquarie Data Centres' existing Macquarie Park campus at 17-23 Talavera Road. Its three buildings, IC2, IC3 East and IC3 SuperWest, reach 65MW once the 47MW SuperWest building is fully built, according to the company's FY26 results.
Macquarie Data Centres proposes air-cooled chillers for Alma Road
Macquarie Data Centres plans to cool the buildings with about 135 air-cooled chillers on the roof, backed by chilled water buffer tanks. The chillers would use free cooling, drawing on cool outside air in place of their compressors when conditions allow. The report says the design "supports a closed loop system which minimises the use of water", and confirmation of water pressure and flow from the utility is pending.
Goodman's Project Apollo, at 4-10 Talavera Road, was approved on 2 September 2026 with a 135MW power cap and a water-cooled design. Its assessment report describes 36 open-circuit evaporative cooling towers.
New South Wales published its data centre guidelines in August 2026, covering energy and water use, renewable energy supply and community benefits. Apollo's consent conditions require firmed renewable supply matched to the whole load and annual reporting of measured power and water efficiency. Macquarie Data Centres' report says the guidelines "will be addressed as part of the EIS submission".
What to watch
The department's requirements. The planning department is preparing them. They will set the scope of the company's environmental impact statement.
The environmental impact statement. The company says it will address the August 2026 guidelines there. It will also lodge the height variation request and the final battery design with it.
Funding. Macquarie Technology said in July 2026 it was exploring capital recycling of existing assets and development partnerships to fund the build. It paid A$240 million for the land.
Keep reading the market
Get The Strategic Brief in your inbox every Thursday.
The leading Australian data centre and AI infrastructure newsletter.
Your Next Read

Macquarie Technology’s road to 200MW

Macquarie Technology buys room to build 200MW in Sydney's north

Stockland wins 49MW Macquarie Park consent under new NSW rules
Latest Headlines
Sydney's data centre pipeline sheds four early-stage plans
20 Nov 2026NEXTDC lifts FY27 guidance, weighs S4 joint venture
20 Nov 2026Stockland plans A$5bn Kemps Creek AI data centre with EdgeConneX
20 Nov 2026Greg Goodman makes case for A$15bn data centre builds
20 Nov 2026Anthropic IPO priced at US$83, valuing it at US$1.5 trillion
20 Nov 2026
Interested in reaching this audience? Advertise with us.